Answers · from Chapter 63: Hardening
Does a Faraday cage protect electronics from EMP?
Does a Faraday cage protect electronics from EMP?
A properly engineered shield can weaken the fields, if it is continuous and every cable entering it is treated. Shields fail at seams, gaps and penetrating wires. For trash cans, microwave ovens and foil wraps, the sources the chapter opened held no shielding measurement, so it rates the popular claim Untested.
What a shield does
A Faraday cage is a conductive barrier placed between a field and the equipment it should not reach. It works two ways at once: part of the incoming wave is reflected at the surface, and part is absorbed as it passes through the metal. Absorption is set by skin depth. Each skin depth of thickness cuts the field by about 8.686 dB, and copper's skin depth shrinks as frequency rises: 8.5 mm at 60 Hz, 0.066 mm at 1 MHz. In the book's calculated example, 0.5 mm of copper absorbs about 66 dB at 1 MHz but 0.5 dB at 60 Hz, plus reflection.
The fast part of a high-altitude pulse, E1, rises in nanoseconds, so most of its energy sits at high frequencies, where thin metal works well. A useful scale for the numbers: 20 dB lets a tenth of the field through, 30 dB about 3.2 percent, and 80 dB only 0.01 percent. CISA's Level 4 asks for 80+ dB through 10 GHz.
Where real shields leak
The metal is rarely the weak point. MIL-STD-188-125-1 names the failures: seams, apertures and conductors that pass through the wall. A deliberate waveguide entry passes only frequencies above its cutoff, c/(2a), 1.5 GHz at 10 cm wide (the book's arithmetic). A power or signal cable entering without filtering carries the pulse straight inside. The EMP Commission found ordinary metal boxes around control equipment inadequate as Faraday cages, being built for weather and modest physical security.
Trash cans, microwave ovens and foil
CISA's 2019 guidelines are the one government source the chapter found that discusses these expedients. Its advice for stored spares is an insulating bag inside heavy-duty aluminum foil, seams overlapped, in at least two complete layers where possible. It gives a standard Mylar food bag little credit. It says metal trash cans are usually not reliable unless the gaps at lid, handles and base are closed against radio waves, and that a microwave oven can serve for small items but should first be checked for phone or radio reception inside. CISA also notes that small handheld devices without long antennas or cords are relatively immune.
A reception check is not a decibel measurement across the E1 band, and the sources the chapter opened held no shielding figures for any of the three. Hence the rating: Untested. The chapter's safety box: never turn an oven on with equipment inside.
What else reduces exposure
CISA's Level 1 advice: unplug non-essential equipment at the equipment end, since long cables act as antennas, and where possible coil what stays connected. Surge protectors with fast response help, though CISA warns that the metal-oxide varistors inside many of them may catch fire when they fail. CISA suggests ferrite beads on connected cables; fiber with no metal breaks the path. For the slow E3 and solar-storm side, which mostly affects long power lines, see the page on what a Carrington solar storm would do to the grid.
What Chapter 63 covers
Chapter 63 treats pulse and geomagnetic disturbance as design loads, covering shielding, protection levels and the Commission's tests.
Sources
- CISA, EMP Protection and Resilience Guidelines for Critical Infrastructure and Equipment, v2.2 (2019)
- DHS S&T, Electromagnetic Pulse Shielding Mitigations (2022)
- Department of Defense, MIL-STD-188-125-1 (1998)
- M. Peng, F. Qin, Clarification of Basic Concepts for EMI Shielding Effectiveness, arXiv:2112.03272
- EMP Commission, Critical National Infrastructures (2008)
Read more in Chapter 63: Hardening, part of Volume III: Off-Grid Solutions. All answers · Formats and prices