Volume III · Part XIV: The Homestead Microgrid · Chapter 63

Hardening

EMP and geomagnetic disturbances as engineering loads, how shields work, where they leak, and what foil, bags and trash cans do.

A guide to the chapter, written for this site. It describes the chapter; it is not an extract from it.

What the chapter covers

This chapter treats electromagnetic pulse and geomagnetic disturbance as engineering loads to design against. It starts with the three parts of a high-altitude pulse described by the EMP Commission's 2004 and 2008 reports: the nanosecond E1, the lightning-like E2 and the slow E3 that drives currents into long lines. It gives the IEC 61000-2-9 E1 waveform as Metatech's Meta-R-320 reports it, and the geomagnetic field benchmarks in NERC TPL-007-4 and CISA's 2019 guidelines, with CISA's 2022 finding that E3 and geomagnetic effects mostly need lines longer than 10 km. The shielding section explains reflection, absorption and skin depth, why thin copper blocks megahertz fields but not 60 Hz ones, and why real shields fail at seams, openings and every wire that passes through. Decibels are translated into fractions that pass, and the military and CISA protection levels are compared. Practical measures follow: unplugging at the equipment end, surge protection, ferrites and fiber. The chapter rates the popular claim for trash cans, microwave ovens and foil wraps Untested, and closes with the EMP Commission's vehicle and computer tests. Check the code in force where you are.

Claims the chapter rates

Each claim gets one rating on the book's scale. How the ratings work.

ClaimRatingKind
A metal trash can, a microwave oven or a wrap of aluminum foil shields stored electronics from EMP (popular claim)Untestedempirical
Vehicles parked during simulated EMP exposure showed no effects; some running vehicles stalled (EMP Commission tests, 2008)Examined, not replicatedempirical

Key numbers

IEC 61000-2-9 E1 reference peak field
50 kV/m, 2.47 ns rise (Meta-R-320 (Metatech, 2010))
CISA E3 planning field (CONUS, southern US)
85 V/km, 1 mS/m ground (CISA EMP guidelines v2.2 (2019))
NERC geomagnetic benchmark field
8 V/km (12 V/km local) (NERC TPL-007-4)
Top shielding level in CISA's scheme (Level 4)
80 dB or more, through 10 GHz (CISA EMP guidelines v2.2 (2019))
Field at which some computer failures can be expected (EMP Commission tests)
3 to 6 kV/m (EMP Commission, Critical National Infrastructures (2008))

Questions this chapter answers

What are the E1, E2 and E3 parts of a high-altitude EMP?

E1 is the fast component, rising in under one to a few nanoseconds and coupling into short wires and electronics. E2 behaves much like lightning in its timing. E3 is slow, can last a minute or more, and induces quasi-direct current in long transmission lines; Metatech's 2010 study calls the methods for analyzing E3 and geomagnetic-storm coupling nearly identical.

Why does a thin copper sheet block radio but not 60 Hz fields?

A conductor attenuates a field by about 8.686 dB for each skin depth of thickness, counting absorption alone. In the book's calculated example, copper's skin depth is 0.066 mm at 1 MHz but 8.5 mm at 60 Hz, so 0.5 mm of copper absorbs about 66 dB at 1 MHz and only about 0.5 dB at 60 Hz. Reflection adds to these figures. Low-frequency magnetic fields are hard to stop.

Where do real shields fail?

Shields fail at seams, apertures and every conductor through the wall, per MIL-STD-188-125-1. A deliberate waveguide entry passes only frequencies above its cutoff, c/(2a), which is 1.5 GHz when the wide side is 10 cm (the book's arithmetic). A cable entering unfiltered carries the pulse inside. The EMP Commission judged the metal boxes around control-system electronics inadequate as Faraday cages, since they are built for weather and modest physical security.

Do sites far from long power lines face E3 damage?

CISA's 2022 resilient-power guidance says E3 and geomagnetic effects are limited to conducting lines longer than 10 km, and an islanded site is unlikely to be damaged by them "except under extenuating circumstances", assuming its power equipment is in reasonable shape. E1 is a separate question: it couples into short cables and electronics, which is what shielding and surge protection address.

Selected sources

  • EMP Commission, Volume 1, Executive Report (2004)
  • EMP Commission, Critical National Infrastructures (2008)
  • E. Savage, J. Gilbert, W. Radasky, The Early-Time (E1) HEMP, Meta-R-320 (Metatech for ORNL, 2010)
  • J. Gilbert et al., The Late-Time (E3) HEMP, Meta-R-321 (Metatech for ORNL, 2010)
  • CISA, EMP Protection and Resilience Guidelines for Critical Infrastructure and Equipment, v2.2 (2019)
  • CISA, Resilient Power Best Practices for Critical Facilities and Sites (2022)
  • M. Peng, F. Qin, Clarification of Basic Concepts for EMI Shielding Effectiveness, arXiv:2112.03272
  • Department of Defense, MIL-STD-188-125-1 (1998)
  • DHS S&T, Electromagnetic Pulse Shielding Mitigations (2022)

More on this chapter

Related chapters

This chapter is in Volume III: Off-Grid Solutions. Drafted and twice audited; chapter text final. Formats and prices · All chapters