Volume II · Part IX: Materials: How the Parts Come to Exist · Chapter 37
Conductors
Copper and aluminum, the IACS standard, the AWG ladder, ampacity as a heat limit, skin effect and why aluminum house wiring failed.
A guide to the chapter, written for this site. It describes the chapter; it is not an extract from it.
What the chapter covers
This chapter treats wire as an engineered part with its own history. It starts with resistivity: annealed standard copper at 1.7241 µΩ·cm, and commercial hard-drawn aluminum as the Bureau of Standards measured it in 1912, which conducts 61 percent as well for the same section but about twice as well per unit mass. It follows how the International Annealed Copper Standard was agreed between 1907 and 1913, why it is a reference and not a ceiling, and how resistance climbs with temperature at 0.00393 per degree Celsius. Wire drawing and annealing are described in principle, then the American Wire Gage: a geometric series devised in 1857 whose numbering roughly tracks the die passes used for fine wire. A section argues that current capacity belongs to the installation, not the wire; heat, insulation and surroundings set it, and codes turn that into allowable currents. Skin effect and litz wire follow, then insulation from rubber to XLPE and EPR. The longest section is the aluminum branch-circuit wiring of about 1965 to the mid-1970s, where the Bureau and the Consumer Product Safety Commission traced failures to connections. Two rated boxes, both Proven, cover ampacity and the aluminum hazard. A safety box covers lead solder, flux fumes and terminations.
Claims the chapter rates
Each claim gets one rating on the book's scale. How the ratings work.
| Claim | Rating | Kind |
|---|---|---|
| Ampacity is a thermal limit set by insulation and installation, not a property of the metal | Proven | empirical |
| The aluminum-wiring hazard shows up at connections | Proven | empirical |
Key numbers
- Copper resistivity, IACS annealed standard (20 °C)
- 1.7241 µΩ·cm (NBS Handbook 100 (1966))
- Copper temperature coefficient (20 °C)
- 0.00393 per °C (NBS Handbook 100 (1966))
- Commercial hard-drawn aluminum conductivity (1912)
- 61 % IACS by volume, 200.7 % by mass (NBS Circular 31 (1912))
- AWG step ratio
- 1.1229 (39th root of 92) (NBS Handbook 100 (1966))
- Pre-1972 aluminum-wired homes, connection hazard
- 55 times more likely (survey cited) (CPSC Pub. 516 (2011))
Questions this chapter answers
Why is aluminum used for wire if copper conducts better?
Aluminum is lighter, which offsets its lower conductivity. Measured by the Bureau of Standards in 1912, commercial hard-drawn aluminum conducts 61 percent as well as copper at equal cross-section, but its density is 2.70 g/cm³ against 8.89, so per unit mass it carries about twice as much. Aluminum suits overhead lines and large feeders, where weight and price per ampere count; copper suits places where space and connections count.
Does a wire have a fixed current rating?
A wire has no fixed current rating; the chapter rates as Proven that ampacity is a thermal limit set by insulation and installation, not by the metal. Current heats the wire until heat out equals heat in, and the insulation and surroundings decide what temperature is acceptable. Codes then set allowable currents; check the code in force where you are.
Why does the American Wire Gage use such odd numbers?
J. R. Brown fixed No. 0000 and No. 36 in 1857 and filled the sizes between in 39 equal-ratio steps of about 1.1229. Three gauge numbers double or halve the area. The numbers run backwards because they roughly follow the successive passes of fine wire through drawing dies.
Why was aluminum house wiring a fire risk?
Aluminum wiring's fire risk was at the connections, a point the chapter rates Proven. Oxide, creep, thermal expansion and fretting at screw terminals let joints run hot. CPSC cites a survey finding pre-1972 aluminum homes 55 times more likely to have an outlet reach fire-hazard conditions. CPSC advises a qualified electrician; check the code in force where you are.
Selected sources
- NBS, Copper Wire Tables, Circular 31, 1st ed. (1912)
- NBS Handbook 100, Copper Wire Tables (1966)
- NBS, Radio Instruments and Measurements, Circular 74 (1918)
- J. Bucknall Smith, A Treatise upon Wire, its Manufacture and Uses (1891)
- J. A. Shea and S. P. McMullan, Developments in the Manufacture of Copper Wire, Bell System Technical Journal 6 (1927)
- US Coast Guard, 33 CFR 183.425, boat electrical conductors
- L. S. Fifield et al. (PNNL), Status of Cable Aging Knowledge Gaps, PNNL-34863 (2023)
- US CPSC, Repairing Aluminum Wiring, Pub. 516 (2011)
- NBS, Aluminum Branch-Circuit Wiring, NBSIR 75-723 (1975)
- W. J. Meese and R. W. Cilimberg, Electrical Connections for Branch Circuit Wiring, NBS Building Science Series 63 (1975)
- Directive 2011/65/EU (RoHS 2)
- USGS, Mineral Commodity Summaries 2025, Copper
Related chapters
This chapter is in Volume II: System Anatomies. Drafted and twice audited; chapter text final. Formats and prices · All chapters