Is old aluminum house wiring dangerous?

Is old aluminum house wiring dangerous?

The documented hazard sits at the connections, not along the run. Pre-1972 aluminum branch wiring oxidizes, creeps and expands at screw terminals, and joints can run hot. CPSC accepts three permanent repairs and advises a qualified electrician. For any wiring work, check the code in force where you are.

Evidence rating: Proven. Claim rated: The aluminum-wiring hazard shows up at connections. How the ratings work.

Where it came from

A copper shortage in the mid-1960s pushed builders toward aluminum for branch circuits, the ordinary outlet and light circuits of a house. Chapter 37 places the practice between roughly 1965 and the middle of the 1970s, and by 1974 close to two million homes had it. The documented trouble was at the ends of the runs, not along them. The Bureau of Standards measured commercial hard-drawn aluminum in 1912 at 61 percent of copper's conductivity at equal cross-section, so a branch circuit needs a larger aluminum wire for the same current.

What the record shows

The Consumer Product Safety Commission (Pub. 516, 2011) cites a survey by the Franklin Research Institute. According to CPSC, one or more outlet connections reaching fire-hazard conditions was "55 times more likely" in homes wired with pre-1972 aluminum. On 28 April 1974 a fire at Hampton Bays, New York, killed two people.

Why the connections fail

J. Rabinow's 1974 memorandum for the Bureau named four troublesome properties of aluminum: high thermal expansion, creep, or stress relaxation, a hard and brittle oxide that insulates, and higher resistance than copper. William Abbott of Battelle, as the Bureau summarized his testimony, put the cause in fretting. Tiny movements between wire, plate and screw as the joint heats and cools wear the contact and build oxide until it runs hot. Inspectors surveyed by UL also reported corrosion from mixed metals or damp at failed connectors.

The chapter rates the claim that the hazard shows up at connections Proven. What stays open is the part played by the old alloy. Rabinow blamed its stress relaxation, while Battelle found no link between that, or any measurable mechanical property, and how terminations performed. No current national count of unrepaired homes was found.

What CPSC accepts as a fix

CO/ALR devices did better with the newer alloy wire, and CPSC finds them better than ordinary devices on old wire when carefully installed. Even so, those devices failed in its laboratory tests, and CPSC treats them as an incomplete repair at best. It puts the primary blame on the aluminum wire. The permanent repairs it accepts are three: replacing the wire with copper, or attaching copper pigtails with either COPALUM crimp connectors or AlumiConn connectors. Its advice is to hire a qualified electrician. Local rules govern electrical work, so check the code in force where you are.

What Chapter 37 covers

Chapter 37 covers copper and aluminum resistivity, the IACS standard, the AWG ladder, ampacity as a heat limit, skin effect and litz wire, insulation materials, and the aluminum branch-circuit record.