Volume III · Part XIV: The Homestead Microgrid · Chapter 62

Distribution, Grounding & Protection

Wire sizing and voltage drop, fuses and breakers, DC fault current, grounding versus bonding, ground rods, GFCI and AFCI, and backfeed.

A guide to the chapter, written for this site. It describes the chapter; it is not an extract from it.

What the chapter covers

This chapter covers the wiring between a small power system's sources and its loads, and the devices that keep a fault from becoming a fire or a shock. It opens with the problems inspectors kept finding, as listed in John Wiles's 2001 Sandia guide, which describes the 1999 National Electrical Code. It then works through ampacity and voltage drop on the round-trip loop, with the book's own examples at 12 V, 24 V and 120 V and Wiles's remote-cabin run. Overcurrent protection follows: thermal and magnetic trips, the 125 percent and 156 percent sizing rules as Wiles reports them, and interrupting ratings, set against the thousands of amperes a single charged battery can deliver into a short. A vocabulary section separates grounded conductors, bonding, equipment grounding conductors and grounding electrode conductors, using OSHA's definitions. O. S. Peters's 1918 Bureau of Standards measurements of driven pipes show why an earth rod cannot be counted on to trip a breaker. The chapter closes with ground-fault and arc-fault interrupters, generator and inverter backfeed, and inrush current. Check the code in force where you are.

Claims the chapter rates

Each claim gets one rating on the book's scale. How the ratings work.

ClaimRatingKind
A ground rod alone will not reliably trip a breaker; the equipment grounding conductor clears case faultsProvenempirical
Arc-fault circuit interrupters reduce fires from arcing faults in branch wiringPlausibleempirical

Key numbers

Share of a driven pipe's resistance in the nearest few feet of soil
about 90 percent within 6 to 10 ft (Peters, NBS Technologic Paper 108 (1918))
Fault current from one charged 6 V, 220 Ah battery
about 8,000 A for a fraction of a second (Wiles, SAND2001-0674 (2001))
Available current at receptacles, UL survey of 1,590 in 80 homes
300 A average (Lee, Trotta and King, CPSC AFCI paper)
Minimum driven rod length, 1999 NEC as Wiles reports it
8 ft (2.4 m) (Wiles, SAND2001-0674 (2001))
Book's example, 8 ft rod at 120 V
about 31 ohms, at most about 3.9 A (Book's arithmetic from Peters (1918))

Questions this chapter answers

Why is a low-voltage DC run so sensitive to wire size?

Voltage drop depends on current and on resistance over the whole out-and-back loop. In the book's example, 240 W carried 15 m at 12 V means 20 A, and AWG 10 loses 1.97 V, or 16.4 percent; AWG 4 brings that to 0.49 V. The same load at 24 V needs only 10 A and loses 0.98 V on AWG 10. Check the code in force where you are.

Can a ground rod alone trip a breaker on a fault?

Ground rods alone cannot reliably trip breakers; Peters measured driven pipes from 22.5 to 167 ohms, varying several hundred percent with season. In the book's example an 8 ft rod near 31 ohms lets 120 V push at most about 3.9 A, which a 15 A breaker carries indefinitely. The equipment grounding conductor, a metal path to the source, clears case faults. Check the code in force where you are.

Why does a battery bank need fuses or breakers with a high interrupting rating?

A charged battery can drive enormous current into a short. Wiles gives about 8,000 A for a fraction of a second from one 6 V, 220 Ah battery. Listed DC breakers he reports are rated 3,000 to 25,000 A, and current-limiting fuses up to 20,000 A. Glass and automotive fuses fall short, and DC arcs persist longer than AC arcs. Check the code in force where you are.

How should a generator be connected to a house?

A generator connects to a house only through a listed transfer switch or interlock, the chapter says. NEC Article 702 covers optional standby systems. Otherwise power can flow backward through the utility transformer and energize a line that crews believe is dead. The utility's interconnection agreement also governs it; check the code in force where you are.