How do I ground a solar system?
How do I ground a solar system?
Wiles's 2001 Sandia guide, describing the 1999 NEC, lists an equipment grounding conductor from every module frame and inverter case back to the source, sized from the overcurrent device, plus an earth electrode; Wiles also suggests one neutral-to-ground bond. The electrode ties the system to earth but cannot reliably clear faults. Check the code in force where you are.
Four words, four wires
Much of the trouble with grounding is vocabulary, so Chapter 62 separates terms using OSHA's definitions. A grounded conductor is a circuit wire deliberately tied to earth; in house AC wiring that is the neutral, and it carries current whenever a load runs. Bonding joins metal parts into one continuous conductive path and needs no earth at all. The equipment grounding conductor (EGC), the bare or green wire, ties the non-current-carrying metal of equipment back to the grounded conductor at the source; it carries nothing in normal use. The grounding electrode conductor links that point to the rod or other electrode in the soil.
The equipment grounding conductor is the fault path
If a live wire touches a metal case, the EGC returns the fault current to the source through low-resistance metal. The current climbs far past the breaker rating and the breaker opens. OSHA requires that path to be permanent, continuous and effective.
Two points follow, as John Wiles's 2001 Sandia guide reports the 1999 National Electrical Code. Wiles suggests joining neutral and EGC at a single point, the load center, when a generator or inverter supplies one; the Code, he reports, wants no normal current on grounding wires. And the EGC size follows the fuse or breaker upstream rather than the load; under that edition's table a 400 A fuse needed 3 AWG or larger, and when circuit wires are upsized for voltage drop, the EGC grows with them. Wiles also reports that the 1999 code wanted module frames and inverter cases grounded whatever the system voltage.
The earth electrode
The rod ties the system to earth potential, bleeds off static and induced charge, and offers surges a path. Wiles reports the 1999 code minimum as a corrosion-resistant rod at least 5/8 in (16 mm) across and at least 8 ft (2.4 m) driven, with DC and AC electrodes common or bonded, and he suggests an extra electrode near the array.
Why the rod cannot replace the EGC comes from O. S. Peters's 1918 Bureau of Standards measurements. About 90 percent of a driven pipe's resistance lies in the nearest 6 to 10 ft of soil, measured pipes ranged from 22.5 to 167 ohms, and readings swung by several hundred percent with the seasons. Peters judged parallel pipes usually more economical than driving deeper.
The book's worked example
Assume an 8 ft, 5/8 in rod in soil of Peters's 7,420 ohm-cm. The formula gives about 31 ohms. A 120 V fault whose only return is that rod and the earth can push at most about 3.9 A, which a 15 A breaker will carry without tripping. Peters's own safety criterion would need 10 ohms or less at 15 A. So the rod is measured, not assumed, and the metal EGC does the fault clearing.
Check the code in force where you are. Lightning protection is a separate subject; see how lightning grounding works.
What Chapter 62 covers
Chapter 62 covers wire sizing and voltage drop, fuses, breakers and interrupting ratings, DC fault current, grounding and bonding, ground rods, GFCI and AFCI devices, and generator and inverter backfeed.
Sources
- J. Wiles, Photovoltaic Power Systems and the National Electrical Code, SAND2001-0674 (Sandia, 2001)
- O. S. Peters, Ground Connections for Electrical Systems, NBS Technologic Paper 108 (1918)
- 29 CFR 1910.304 and 1910.399 (OSHA)
Read more in Chapter 62: Distribution, Grounding & Protection, part of Volume III: Off-Grid Solutions. All answers · Formats and prices