Why is backfeeding a generator dangerous?
Why is backfeeding a generator dangerous?
A generator tied into house wiring without a transfer switch can push power backward through the utility transformer, which steps it up to distribution voltage on a line crews believe is dead. The CPSC calls this an electrocution risk. A generator connects through a listed transfer switch or interlock. Check the code in force where you are.
What backfeed is
Backfeed is power flowing the wrong way: from a home generator or inverter, out through the building's service, and onto the utility's lines. It can happen when a generator is wired into a building without a transfer switch.
Why the transformer raises the voltage
A transformer works in both directions. Push 240 V into the service drop from inside the house, and the same transformer steps it up, so distribution voltage appears at the pole, on a conductor the crew presumes dead.
The US Consumer Product Safety Commission's 2021 safety alert on portable generators names the danger plainly: backfeeding creates "electrocution risk to utility workers and neighbors" who share the same utility transformer. The risk does not stay on the generator owner's property.
The only connection the chapter describes
Chapter 62 gives one answer: a standby generator connects to a building through a listed transfer switch or interlock, the chapter says. NEC Article 702 covers optional standby systems. The utility's interconnection agreement, plus local code, decides what may be connected and how. Check the code in force where you are.
Inverters raise the same question
The same physics applies to a solar or battery inverter. As NREL's 2020 roadmap on grid-forming inverters is cited in the chapter, grid-following inverters are designed to switch off when grid voltage disappears. A grid-forming inverter can keep running as an island, so it needs islanding protection; Chapter 46, as Chapter 62 notes, names IEEE 1547 and UL 1741 for that scope.
A second, quieter problem: the neutral bond
John Wiles's 2001 Sandia guide notes that small generators may bond the neutral and grounding conductors to the frame at their outlets. Wiles suggests a single bond, made in the load center, when a generator or inverter feeds one, so that normal current stays off the grounding wires, which the Code, he reports, requires. Which wiring suits a particular unit is left to the code and an electrician.
Starting current
Inside the system, lamps and compressors draw starting current several times their steady level, the CPSC paper notes. For that reason Wiles favors time-delay fuses or inverse-time breakers wherever motor starts and lightning transients occur, and an inverter needs enough capacity to start the biggest motor it serves.
What Chapter 62 covers
Chapter 62 covers wire sizing and voltage drop, fuses and breakers, DC fault current, grounding and bonding, ground rods, GFCI and AFCI devices, and generator and inverter interconnection.
Sources
- US CPSC, Portable Generator Hazards, Pub. 5123/102021 (2021)
- J. Wiles, Photovoltaic Power Systems and the National Electrical Code, SAND2001-0674 (Sandia, 2001)
- Y. Lin et al., Research Roadmap on Grid-Forming Inverters, NREL/TP-5D00-73476 (2020)
- D. A. Lee, A. M. Trotta, W. H. King, Jr., New Technology for Preventing Residential Electrical Fires (CPSC)
Read more in Chapter 62: Distribution, Grounding & Protection, part of Volume III: Off-Grid Solutions. All answers · Formats and prices