How big a battery bank do I need for off-grid solar?
How big a battery bank do I need for off-grid solar?
Bank size is the daily energy drawn at the battery terminals times the days the bank must carry the load unaided, divided by the allowed depth of discharge and a temperature factor. The result is then checked against the rate it will actually be drawn at.
The method
Chapter 61 sizes a bank in a fixed order: the daily load first, then how many days the bank must carry it, how deeply it may be discharged, temperature, discharge rate and finally voltage. Each step is a stated assumption, and the chapter says its numbers are an example, not a recommendation.
The book's worked example
- Load. The example house draws 3.0 kWh a day, measured at the battery terminals, so inverter losses are already inside that figure.
- Autonomy. Days the bank must carry the load with no charging, set by the site's weather and by whatever else can charge it. The example takes three, so the bank must supply 9.0 kWh.
- Depth of discharge. PNNL's 2022 assessment caps lead-acid at 80 percent, to keep it from sitting long below 20 percent state of charge, where sulfation does lasting harm. In the example the bank reaches that floor only at the end of the third day, not nightly.
- Temperature. The Bureau of Standards measured vehicle lead-acid cells in 1920 losing about 13 percent of capacity for each 10 °C of cooling at the 5-hour rate. Measured from 20 °C, that is 87 percent for a 10 °C room on those vehicle cells; a stationary battery's maker publishes its own curve.
Put together, 3.0 × 3 divided by (0.80 × 0.87) is about 12.9 kWh nominal. That is about 539 Ah at 24 V, 269 Ah at 48 V or 1,078 Ah at 12 V, and the daily draw is about 23 percent of the bank (the book's arithmetic). At 50 percent depth the same house would need about 20.7 kWh.
Rate and voltage
The Bureau's 1920 rule is that capacity falls as the discharge gets faster. PNNL builds this in by assuming a shallower usable depth of discharge for lead-acid: 68.1 percent at a 4-hour discharge and 58.0 percent at 2 hours, down from its 80 percent cap. The example averages 125 W, but a 2,500 W inverter at full output pulls about 134 A from 24 V, roughly C/4. Size energy at the rate the bank will really see and check peak current against the maker's limit. At 48 V the same load draws about 67 A, but Sandia's 2001 code guide, which describes the 1999 NEC, flags shock hazards from 50 V up, and a 48 V lead-acid bank of 24 cells reaches 57.6 V at the Bureau's 2.4 V per cell charging maximum. Check the code in force where you are.
How Chapter 58's bank differs
Chapter 58 sizes its own example on different assumptions, following Sandia's worksheet: 4 days, 50 percent depth and Sandia's 0.9 temperature default, giving 915 Ah at 48 V, about 44 kWh nominal lead-acid. Its 80 percent case needs 572 Ah, about 27 kWh. Neither figure is wrong; each follows from its stated inputs.
What Chapter 61 covers
The chapter covers storage on three time scales: bank sizing, charging stages and state-of-charge readings, cycle and calendar life, choosing a chemistry, and flywheels and hydrogen.
Sources
- V. Viswanathan et al., 2022 Grid Energy Storage Technology Cost and Performance Assessment, PNNL-33283 (2022)
- US Bureau of Standards, Operation and Care of Vehicle-Type Batteries, Circular 92 (1920)
- J. Wiles, Photovoltaic Power Systems and the National Electrical Code, Suggested Practices, Sandia SAND2001-0674 (2001; describes the 1999 NEC)
- Sandia National Laboratories, Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices, SAND87-7023 (updated March 1995)
Read more in Chapter 61: Storage, part of Volume III: Off-Grid Solutions. All answers · Formats and prices