Volume III · Part XIV: The Homestead Microgrid · Chapter 61

Storage

Sizing a battery bank, charging and state of charge, cycle and calendar life, choosing a chemistry, flywheels and hydrogen.

A guide to the chapter, written for this site. It describes the chapter; it is not an extract from it.

What the chapter covers

This chapter treats storage on three time scales: seconds for flywheels, days for a battery bank and seasons for hydrogen. It opens with the 2011 Stephentown flywheel plant and separates a store's power rating from its energy rating, then compares round-trip efficiencies on stated bases. The core is a battery bank sized in order: daily load at the terminals, days of autonomy, depth of discharge, temperature, discharge rate and voltage, worked for an example house at 3.0 kWh a day to about 12.9 kWh nominal, with each factor credited to PNNL's 2022 assessment or the Bureau of Standards' 1920 vehicle battery circular. Series and parallel strings and fault current follow, citing Sandia's 2001 guide to the 1999 NEC. The charging section explains the current-limited, constant-voltage and float stages, Yuasa's temperature compensation and three ways to read state of charge. A section on life separates cycle life from calendar life and insists every figure name its cells, its test and its end-of-life criterion. The chapter ends with chemistry choice, flywheel standby losses rated Plausible and hydrogen round trip through a PEM fuel cell rated Examined, not replicated.

Claims the chapter rates

Each claim gets one rating on the book's scale. How the ratings work.

ClaimRatingKind
An energy flywheel loses up to a few percent of its stored energy per hour standing, so it stores for hours, not daysPlausibleempirical
Electricity stored as hydrogen and returned through a PEM fuel cell comes back at roughly 35 to 50 percent of what went inExamined, not replicatedempirical

Key numbers

Example bank, 3.0 kWh/day for 3 days
about 12.9 kWh nominal (book's arithmetic) (PNNL 2022 DOD limit; Bureau of Standards 1920 temperature figure)
Lead-acid depth-of-discharge limit
80 percent (PNNL-33283 (2022))
Cold capacity loss, vehicle lead-acid cells at the 5-hour rate
about 13 percent per 10 °C (US Bureau of Standards Circular 92 (1920))
Round trip, DC basis
Li-ion about 90 percent; lead-acid 77 to 87 percent (PNNL-33283 (2022))
LFP calendar life assumed for costing
16 years (PNNL-33283 (2022))

Questions this chapter answers

How big a battery bank does the chapter's example house need?

The example draws 3.0 kWh a day from the battery, must ride through three days, and takes 0.87 for a 10 °C battery room with lead-acid held to the 80 percent discharge limit PNNL uses. That gives about 12.9 kWh nominal, 539 Ah at 24 V or about 269 Ah at 48 V, the book's arithmetic. For batteries and wiring, check the code in force where you are.

What ends a battery bank's life first?

For a lithium bank sized for several days of autonomy, calendar age ends it first, on this book's comparison of one maker's laboratory data. The example cycles about 23 percent a day, where Saft's LFP data allow more cycles than sixteen years of days, and PNNL assumes 16 years of calendar life for LFP. For wiring and battery choices, check the code in force where you are.

How long can a flywheel hold its energy?

A flywheel holds its energy for hours, not days (rated Plausible); Sandia's 2013 handbook puts standby loss typically under 25 W DC per kWh for magnetic bearings in vacuum, about 2.5 percent an hour (converted); for mechanical bearings Boeing puts it at 3 to 5 percent an hour or more. These come from developers and handbooks, and the chapter found no independent test of a commercial unit.

How much electricity comes back from hydrogen storage?

NASA Glenn's closed PEM test bed returned 50.4 percent over one cycle on one rig, but no more than 37 percent across a five-day endurance run, and NASA puts such hardware at 35 to 50 percent; the book rates this Examined, not replicated. Hydrogen is flammable from 4 to 75 percent by volume in air (ILO/WHO ICSC 0001). Recovered heat raises useful output, not the electricity returned.

Selected sources

  • A. A. Akhil et al., DOE/EPRI 2013 Electricity Storage Handbook in Collaboration with NRECA, SAND2013-5131 (Sandia, 2013)
  • V. Viswanathan et al., 2022 Grid Energy Storage Technology Cost and Performance Assessment, PNNL-33283 (2022)
  • US Bureau of Standards, Operation and Care of Vehicle-Type Batteries, Circular 92 (1920)
  • J. Wiles, Photovoltaic Power Systems and the National Electrical Code, Suggested Practices, Sandia SAND2001-0674 (2001; describes the 1999 NEC)
  • GS Yuasa, NP Series Valve Regulated Lead Acid Battery Application Manual
  • C. P. Garcia et al., Round Trip Energy Efficiency of NASA Glenn Regenerative Fuel Cell System, NASA/TM-2006-214054 (2006)
  • ILO/WHO International Chemical Safety Card ICSC 0001, Hydrogen