How do I size an off-grid solar system?
How do I size an off-grid solar system?
Off-grid sizing starts from a list of every load and its daily hours, carries that daily energy back through the inverter, wiring and battery losses, sizes the battery from days of storage and allowed depth of discharge, then sizes the array to refill it in the month where sun is lowest relative to the load.
The order of the work
Chapter 58 follows the 1995 Sandia stand-alone handbook, SAND87-7023. Everything starts with the load list. The array must replace each day's draw in the worst month, the battery to carry them through days the array cannot, and the inverter to start whatever can run together.
The book's worked example and its assumptions
The figures below are the chapter's example household, not a recommendation. Its loads are all 120 V AC and every row is assumed: refrigerator, LED lighting, a well pump, a laptop and network gear, a microwave, a washer used three days a week and standby draw. The audit comes to 3,704 Wh a day, and 2,765 W if all ran together.
- System voltage. That 2,765 W sits in the 1,500 to 5,000 W band of Sandia's Table 1, so Sandia's table allows 24 or 48 V and the example picks 48 V.
- Inverter. Sandia advises at least 125 percent of the simultaneous peak: 3,456 W, met by a 3,500 W unit. Pump starting is a separate surge check against the maker's rating.
- Energy from the battery. The daily load is divided by Sandia's worksheet defaults: 0.85 for DC-to-AC conversion, 0.98 for wiring (range 0.95 to 0.99) and 0.9 for the battery. That gives 4,941 Wh a day, or 102.9 Ah at 48 V. Because daytime loads served straight from the array skip the battery, this leans conservative.
- Battery bank. Sandia's worksheet multiplies that by the storage days, then divides by the allowed discharge depth and by a 0.9 default factor for temperature. The example takes 4 days, its reading of Sandia's chart for 95 percent availability at 3.43 peak sun hours, and 50 percent depth, the figure Sandia's example household used. Result: 915 Ah at 48 V, about 44 kWh nominal lead-acid (the book's arithmetic).
- Array. Sandia sizes by current in the design month. For Birmingham, Alabama, tilted at latitude plus 15 degrees, the weakest month is December, with 3.43 peak sun hours. With Sandia's 0.9 crystalline derate the array needs 33.3 A at 48 V, about 1.6 kW (calculated). Dividing by the PVWatts 14 percent default loss instead gives about 1.7 kW (calculated).
What the method leaves to you
Sandia says there is no single right number of storage days. The chapter states margin once instead of padding each load, and checks inverter efficiency at light load, where the example idles below 7 percent of rating. Sandia's 2001 code guide describes the 1999 NEC, so for wiring, battery and inverter choices, check the code in force where you are.
What Chapter 58 covers
The chapter runs one household through five steps: a load audit, load tiers, the choice of DC or AC bus, sizing, and a matrix of failure modes, with every factor credited to its source. Chapters 59 and 61 refine the array and battery figures.
Sources
- Sandia National Laboratories, Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices, SAND87-7023 (updated March 1995)
- US DOE Energy Saver, Estimating Appliance and Home Electronic Energy Use
- J. Wiles, Photovoltaic Power Systems and the National Electrical Code, Suggested Practices, Sandia SAND2001-0674 (2001; describes the 1999 NEC)
- A. P. Dobos, PVWatts Version 5 Manual, NREL (2014)
Read more in Chapter 58: System Design, part of Volume III: Off-Grid Solutions. All answers · Formats and prices