How does a ground-source heat pump work?

How does a ground-source heat pump work?

A ground-source heat pump uses electricity to move heat out of the ground and up to a useful temperature indoors. A refrigerant boils as it takes heat from fluid in a buried loop, a compressor raises its temperature, and a condenser releases the heat to the building. Its heat output exceeds the electricity it draws.

Evidence rating: Proven. Claim rated: A coefficient of performance above 1 is ordinary and implies no output beyond total input. How the ratings work.

What are the working parts?

A ground-source heat pump has four working parts. In the evaporator a refrigerant boils at low pressure, taking up heat from the cold side, here the fluid circulating through the ground loop. A compressor, usually run by an induction motor, squeezes the vapor so its pressure and temperature rise. In the condenser the hot vapor hands its heat to the building and turns back to liquid. An expansion device then drops the pressure and the loop starts again. Running the cycle the other way cools the building and sends its heat into the ground.

Why use the ground?

Below the first few feet, ground temperature swings less than winter air, so it makes a steadier cold side. That does not make it warm: the system NREL monitored in Ruby, Alaska, was designed for ground at 25 °F. Ground temperature has to be measured locally. The loop can be laid in horizontal trenches, run down vertical boreholes where land is short, sunk as coils in a pond, or replaced by an open loop that draws well water and returns it.

How can it give out more heat than the electricity it uses?

It moves heat rather than making it. The heat drawn from the ground is a real input, but the electricity meter does not record it. The coefficient of performance divides heat delivered by electricity used, so a value above 1 is normal; the book rates that statement Proven, and stresses that output never exceeds all inputs counted together. The ceiling is set by the temperature lift: on the book's standard example, an ideal machine moving heat from 0 °C ground to 35 °C delivery would reach about 8.8; no rating or field result in the chapter comes near it.

What COP do real systems reach?

Ratings and field results differ. ENERGY STAR's criteria, effective 1 January 2012, require closed-loop water-to-air units to reach a heating COP of 3.6 and an EER of 17.1, steady-state ratings on a test stand. In the field, one 36,000 Btu/h unit served by six vertical wells roughly 100 feet deep in Ruby measured an average heating COP of 2.68, from November 2021 to September 2022 by the direct method, which the authors call likely an underrepresentation; its design figure was 2.5. That is one building in climate zone 8, sharing its load with a boiler, not a figure for the class.

How long must the loop be?

That depends on the building, the climate and the ground. An Oak Ridge modeling study of commercial buildings in thirteen US cities found bore lengths per ton of cooling, at each state's median ground conductivity, from 131 feet for a medium office in Seattle to more than 400 feet in Phoenix. The chapter names other drivers across studies. The chapter gives no sizing procedure.

What Chapter 55 covers

Chapter 55, Heat Pumps & Ground Loops, covers the vapor-compression cycle, what COP and EER ratings mean, the measured Alaska system, loop types and the variables that set loop length, how refrigerants are now regulated, and a safety box on refrigerant frostbite, refrigerant venting and trench work. Check the code in force where you are.