What the chapter covers

This chapter explains machines that move heat rather than make it. It starts from the plain comparison: an electric resistance heater converts electricity to heat one for one, a coefficient of performance of 1, while a heat pump delivers several units by carrying heat from a cold place to a warm one. It names the four working parts, the evaporator, the compressor, the condenser and the expansion device, and shows how the same loop runs backward to cool. The Carnot ceiling for a heat pump is set out with the book's own worked example. Rated figures come from the ENERGY STAR criteria for geothermal heat pumps and from the US Federal Energy Management Program's December 2024 purchasing table, and the chapter explains how a cooling rating in EER converts to a COP. One measured case follows: a National Renewable Energy Laboratory study of a ground-source unit in Ruby, Alaska. The chapter then covers the kinds of ground loop, horizontal, vertical, pond and open, and two Oak Ridge National Laboratory studies on how long a vertical bore must be and how grout and pipe choices change that length. It closes with a safety box on refrigerant frostbite, the federal rule against venting refrigerant, and trench work; check the code in force where you are.

Claims the chapter rates

Each claim gets one rating on the book's scale. How the ratings work.

ClaimRatingKind
A coefficient of performance above 1 is ordinary and implies no output beyond total inputProvenempirical

Key numbers

ENERGY STAR closed-loop water-to-air, rated
EER 17.1; COP 3.6 (ENERGY STAR criteria effective 1 Jan. 2012)
Ruby, Alaska ground-source unit, average heating COP, Nov 2021 to Sep 2022
2.68 (one site, climate zone 8) (NREL (2023), DOE/GO-102023-5816)
Carnot COP, 0 °C source to 35 °C delivery
about 8.8 (book's calculation)
Vertical bore length, modeled commercial buildings
131 to over 400 ft per ton (ORNL/LTR-2016/344)
Bentonite grout thermal conductivity
0.38 to 0.45 Btu/h·ft·°F (ORNL/TM-2018/756)

Questions this chapter answers

How can a heat pump put out more heat than the electricity it uses?

A heat pump moves heat instead of making it. The compressor's electricity carries heat already present outdoors or in the ground up to a warmer temperature indoors, and the delivered heat counts both the moved heat and the electricity. Dividing delivered heat by electricity gives a coefficient of performance above 1. Total output never exceeds total input, and the book rates that statement Proven.

What are the main parts of a heat pump?

A heat pump has four main parts: the evaporator takes in heat at low temperature as the refrigerant boils. The compressor, usually driven by an induction motor, raises the vapor's pressure and temperature. The condenser gives the heat up where it is wanted, and the expansion device drops the pressure again. Run backward, the same machine cools the building instead.

What COP do ground-source heat pumps reach?

The rated ENERGY STAR level for closed-loop water-to-air units is a heating COP of 3.6, a steady-state rating. One NREL study of a single unit in Ruby, Alaska, in climate zone 8, measured an average heating COP of 2.68 from November 2021 to September 2022, by the direct method, which the authors call likely an underrepresentation; monthly values ran from 2.51 (November) to 3.20 (July).

How long does a vertical ground loop need to be?

An Oak Ridge study of modeled commercial buildings, not houses, in 13 cities found design bore lengths, per ton of cooling at each state's median ground conductivity, from 131 feet for a medium office in Seattle to more than 400 feet in Phoenix, about 11 to 35 meters per kilowatt on the book's conversion. These are modeled figures, not a rule for any one site.

Does grout matter in a ground loop?

Grout matters in a ground loop: a 2018 Oak Ridge study gives ordinary bentonite grout a thermal conductivity of 0.38 to 0.45 Btu per hour-foot-degree Fahrenheit and enhanced grouts up to 1.6. In ground that conducts heat well, enhanced grout combined with a double U-tube made the modeled bores over 60 percent shorter.