How does an absorption refrigerator work?
How does an absorption refrigerator work?
An absorption refrigerator replaces the compressor with heat. A liquid absorbs refrigerant vapor at low pressure, and heating that solution drives the refrigerant back out at high pressure. The rest of the loop, condenser and evaporator, works as in an ordinary refrigerator.
What replaces the compressor?
A household refrigerator moves heat by boiling a refrigerant at low pressure and condensing it at high pressure, with a motor-driven compressor raising the pressure in between. An absorption machine keeps the evaporator and the condenser and replaces the compressor with a heat-driven stage, a thermal compressor in the US Department of Energy's phrase. It has three parts. In the absorber a liquid soaks up refrigerant vapor while the pressure is low. A small pump then moves that solution to the generator, where heat drives the refrigerant off again at high pressure, ready for the condenser.
Which fluids are used?
Two working pairs dominate absorption machines. With water as refrigerant and lithium bromide absorbing it, a machine makes chilled water down to about 40 °F (4.4 °C, converted), the job of building chillers. Ammonia paired with water goes colder, for duties like cold storage.
How can a gas refrigerator have no pump at all?
Baltzar von Platen and Carl Munters solved that with a third fluid. Their US Patent 1,609,334, granted in December 1926, fills the evaporator and absorber with hydrogen so the whole unit stays at one total pressure. Ammonia still boils in the evaporator because only its own partial pressure counts: in the patent's example the unit sits at 16 atmospheres, of which ammonia accounts for 3.5 and hydrogen 12.5 in part of the evaporator. Gravity does the circulating, since gas carrying ammonia is heavier than hydrogen, and a heated tube acting as a thermosiphon lifts the solution. Hydrogen is flammable at 4 to 75 percent by volume in air (ILO/WHO ICSC 0001).
How efficient is it?
The measure is a thermal coefficient of performance: useful cooling divided by heat put in, leaving out pumps and fans. The book works an ideal ceiling of about 1.84 for 90 °C heat, 30 °C surroundings and a 5 °C cold side, and notes that real single-stage units on the market fall below half that figure. DOE's 2017 fact sheet gives typical full-load values of 0.70 to 0.79 for single-stage lithium-bromide chillers and 1.35 to 1.42 for two-stage ones, at 44 °F chilled water, drawn partly from vendor data. One 2018 ammonia-water-hydrogen prototype measured 0.11 to 0.26, cooling an enclosure at 25 °C.
Can it be compared with an electric refrigerator?
Not directly. An electric machine's COP divides cooling by electricity, and a kilowatt-hour of electricity is not equivalent to a kilowatt-hour of heat. The chapter says a fair comparison first puts both on one input, such as fuel at the power plant, money or carbon.
What Chapter 54 covers
Chapter 54, Absorption Refrigeration, covers the absorption cycle and its ideal limit, the two-tank Icyball and its 1974 Army test, the Platen-Munters refrigerator, the Einstein-Szilard patent and commercial lithium-bromide chillers. Its safety box sets out ammonia's exposure limits and hazards, hydrogen and pressure. Check the code in force where you are.
Sources
- US Department of Energy, Absorption Chillers for CHP Systems, DOE/EE-1608 (2017)
- B. C. von Platen and C. G. Munters, US Patent 1,609,334, Refrigeration (1926)
- A. Najjaran et al., Proceedings of ECOS 2018
- ILO/WHO International Chemical Safety Card ICSC 0414, Ammonia (anhydrous)
- ILO/WHO International Chemical Safety Card ICSC 0001, Hydrogen (April 2014)
Read more in Chapter 54: Absorption Refrigeration, part of Volume II: System Anatomies. All answers · Formats and prices