What is power factor?

What is power factor?

Power factor is the ratio of real power, in watts, to apparent power, in volt-amperes (rms volts times rms amperes). It equals the cosine of the phase angle between voltage and current. At a power factor of 1 every volt-ampere does work; below 1, extra current flows in the wires without delivering energy.

What are real, reactive and apparent power?

Multiply rms voltage by rms current and the result is apparent power, measured in volt-amperes (VA). Only part of that figure leaves the circuit as heat, light or mechanical work. That part is real or true power, in watts. The rest, reactive power, moves into the fields of capacitors and inductors and comes back out each cycle. Its unit is the var, a name the 1956 US Navy manual Basic Electricity builds from the initial letters of volt-ampere-reactive.

Why is there a phase angle at all?

In an inductor the current lags the voltage by a quarter cycle; in a capacitor it leads. Reactance stores energy and hands it back rather than turning it into heat. A load that combines resistance with reactance, such as the book's 30 + j40 Ω coil, has a current angle between fully in step and a quarter cycle out, and the cosine of that angle is the power factor.

What does a worked example look like?

Chapter 35 of The Forbidden Current uses a coil with 30 ohms of resistance and 40 ohms of reactance, an impedance of 50 ohms at 53.1 degrees. Connected to 120 V it draws 2.4 A. That comes to 288 VA apparent, 172.8 W real and 230.4 var reactive. The three numbers form a right triangle, and 172.8 divided by 288 gives a power factor of 0.6.

Why does a low power factor matter?

Reactive current is ordinary current in ordinary conductors, and it heats them even though it delivers no net energy to the load. In the book's example the supply must carry 2.4 A, where a power factor of 1 would need only 1.44 A for the same work.

How is power factor corrected?

A capacitor connected in parallel with an inductive load can supply that load's vars on the spot, so they stop travelling back and forth to the source. For the coil above, the book's worked figure is about 42 µF, which brings the line current down from 2.4 A to 1.44 A. Capacitors stay charged after power is removed: the chapter's safety box gives 8 J stored in 100 µF at 400 V, and cites the OSHA rule on work at generating, transmission and distribution installations: capacitors are disconnected and short-circuited first, with a wait of at least five minutes after disconnection before the short goes on.

Where does power factor appear in grid rules?

Under FERC Order 827, in effect since September 2016, a newly interconnecting non-synchronous generator, wind and solar photovoltaic plants included, must be capable of producing or absorbing reactive power over a range from 0.95 leading to 0.95 lagging, roughly 33 var for each 100 W. Under FERC Order 904, effective 27 January 2025, a transmission provider may no longer bill its customers for reactive power a generator delivers inside that standard range.

What Chapter 35 covers

Chapter 35 builds up to power factor from Ohm's and Kirchhoff's laws, reactance, impedance, resonance and three-phase systems, and closes with a safety box on shock currents and stored charge.

Sources

  • US Navy, Basic Electricity, NAVPERS 10086 (1956), ch. 12
  • FERC, Order No. 827, Reactive Power Requirements for Non-Synchronous Generation, 81 FR 40793 (2016)
  • FERC, Order No. 904, Compensation for Reactive Power Within the Standard Power Factor Range, 89 FR 93410 (2024)
  • 29 CFR 1910.269(w)(1)(i), OSHA capacitor rule

Read more in Chapter 35: Circuits, part of Volume II: System Anatomies. All answers · Formats and prices