Transformers

Closed-core transformers from Budapest, turns ratio and volts per turn, core and copper loss, inrush, oil and paper, rewind limits.

A guide to the chapter, written for this site. It describes the chapter; it is not an extract from it.

What the chapter covers

Chapter 44 opens at the 1885 Inventions Exhibition in South Kensington, where two closed-iron transformers from Budapest stood side by side on one pair of mains, each taking 1,000 volts down to 100. It explains why that parallel layout beat the series string Gaulard and Gibbs had used: an idle unit has to draw almost nothing, and in practice that takes a closed iron path. An evidence box sets the European patent and exhibition dates against William Stanley's Great Barrington plant of 1886. The physics follows. Voltage tracks the turns ratio and current its inverse, while the core's cross-section fixes how many volts each turn can carry, which is why a 60 Hz unit sits nearer saturation on a 50 Hz supply. Magnetizing current, the hysteresis and eddy-current losses in the iron and the resistive loss in the copper explain both laminations and the 2024 US efficiency rule. Leakage and regulation, switch-on inrush, autotransformers, three-phase banks and current transformers come next, then the oil and paper that set how long a power transformer lasts. Rewinding appears only as a concept bounded by core flux, window area and insulation class, and this book does not treat microwave-oven transformers as donor parts.

Claims the chapter rates

Each claim gets one rating on the book's scale. How the ratings work.

ClaimRatingKind
The parallel-connected, closed-core transformer system was demonstrated in Europe before Stanley's Great Barrington installation (popular claim: Stanley or Westinghouse invented the transformer)Provenempirical

Key numbers

ZBD parallel installation, South Kensington, 1885
1,000 V to 100 V, 800 yd line (Fleming 1892, pp. 85-86)
Gaulard-Gibbs efficiency, London trial of 1883
86-89% (Fleming 1892, p. 75 (Hopkinson report))
Inrush peak flux, worst case
up to remanence plus 2x normal maximum (Steinmetz 1909, sec. 102)
US distribution-transformer production set up for GOES cores (DOE wording)
97 percent of units (89 FR 29834 (2024))
Step-up transformer life: ANSI/IEEE assumption vs Reclamation fleet average
20-25 yr assumed at rated conditions vs 40 yr (USBR FIST 3-30, sec. 2)

Questions this chapter answers

How does a transformer change voltage?

Alternating current in the primary sets up a changing flux in an iron core. Because that one flux links both windings turn by turn, the induced voltage per turn is equal on each side. Output voltage therefore follows the ratio of turns, current follows the inverse ratio, and power out equals power in less losses. No wire joins the two windings, which also gives isolation.

Why are transformer cores built from thin laminations?

The changing flux induces eddy currents that circulate inside the iron and waste energy as heat. Laminating the core cuts those currents, and the Zipernowsky-Déri-Bláthy patent of 1885 claims a closed, laminated core for that reason. Silicon steel trims both eddy and hysteresis loss. This core loss runs whenever the unit is energized, with or without a load.

Who invented the transformer?

Credit for inventing the transformer depends on what is counted. Zipernowsky, Déri and Bláthy hold Austro-Hungarian and British patents from March and April 1885, and Fleming places their parallel setup at South Kensington in July 1885. Stanley's application followed in October 1885, and his Great Barrington lights in March 1886. The chapter rates the European-priority claim Proven and calls the credit a matter of definition.

Why must a portable generator never feed house wiring directly?

Tied into a building's wiring with no transfer switch, a generator can push power back out through the utility transformer, and the US CPSC warns this can electrocute line workers and neighbors on that transformer. Standby connections go only through a listed transfer switch or interlock, the chapter says. NEC Article 702 covers optional standby systems. Rules vary by place, so check the code in force where you are.

Selected sources

  • J. A. Fleming, The Alternate Current Transformer in Theory and Practice, vol. II (1892)
  • K. Zipernowsky, M. Déri and O. T. Bláthy, US Patent 352,105, Induction-Coil (1886)
  • W. Stanley, US Patent 349,611 (1886)
  • IEEE Milestone, Alternating Current Electrification, 1886
  • C. P. Steinmetz, Theoretical Elements of Electrical Engineering (1902)
  • C. P. Steinmetz, Theory and Calculation of Transient Electric Phenomena and Oscillations (1909)
  • US DOE, energy conservation standards for distribution transformers, 89 FR 29834 (2024)
  • US Bureau of Reclamation, FIST 3-30, Transformer Maintenance (2000)
  • US CPSC, Portable Generator Hazards, Safety Alert Pub. 5123 (2021)